Specifications:
| ©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. | |
Specifications![]() | |
| Product Code | 103006592-6591![]() |
| General | |
| Topology | Line interactive |
| Configuration | Rack / Tower |
| Commercial References | 103006592-6591 |
| Color | Black |
| Power (VA / Watts) | 2500/2250 |
| Diagnostics | Autotest complete power |
| Yield | > 94% |
| Dimensions H x W x D, mm | 86 x 441 x 634 |
| Weight kg | 33.8 |
| Kit slideways | The 5130 can be deployed in rack or tower style; pedestals and slides are included in the package at no extra cost |
| Emergency remote shutdown (REPO) | Back connector for powering and remote shutdown |
| Entrance | |
| Input connection | (1) IEC-320-C20 |
| Rated voltage | 230 VAC |
| Voltage Range | 160-294V |
| Frequency | 50/60 Hz |
| Frequency range | 47-70 Hz for 50 Hz operation, 56.5-70 Hz for 60 Hz operation |
| Gauge breaker recommended entry | 10A |
| Exit | |
| Output jacks | (8) IEC-320-C13 |
| (1) IEC-320-C19 | |
| Overcurrent protection | Electronic limiter |
| Voltage Regulation (AC) | 184-265 Vac |
| Voltage regulation (battery) | -10% 6% of the nominal |
| Load factor (Cos phi) | 0.9 |
| Transfer time | 1-4 ms typical |
| Crest factor of the load | 3: 1 |
| Load Segments | 2 segments of independent load |
| Batery | |
| Replacement | Hot-swappable internal batteries |
| Test batteries | Weekly battery test without interrupting the load (daily or monthly if required) |
| Battery start | Allows start of UPS without industry |
| Communications | |
| User Interface | ON / OFF Operation indicator, used Power / Battery charge level, state of the controlled outlets |
| Led | 13 status LEDs |
| Standard communication ports | RS-232 port (RJ45) and USB network adapter Optional ConnectUPS-MS, Relay Card / Serial Management Card-MS, RS 232 cable and USB communication Port included |
| Slot for communication | Optional: Network card ConnectUPS-MS, Relay Card / Serial Management Card-MS |
| Software Power Management | Eaton software suite bundled with UPS |
| Environment and safety | |
| Heat dissipation (BTU) | Line: 490 Bat: 2559 |
| Audible noise | Max 45 dBA |
| Operating Temperature | 0 ° C to 40 ° C (Storage: -15 ° C to 50 ° C) |
| Marking Safety | EC; C-Tick; TUVus |
| EMC | IEC / EN 62040-2 EN 50091-2 class B |
| Certifications | IEC / EN 62040-1-1, UL 1778 |
| Relative humidity | 20-95% unfused |
Sold by ComX Computers