Specifications:
| ©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. | |
Specifications![]() | |
| Product Code | 68417![]() |
| General | |
| Topology | On-line double conversion with automatic by-pass and power factor correction |
| Configuration | Rack/Tower |
| Part Number | 68417 |
| Color | metallic grey |
| Rating (VA/Watts) | 3000/2700 |
| Maximum rating with EXB battery units: 2400 W | |
| Dimensions (H x W x D, mm) | 440 x 86 x 640 |
| Weight (kg) | 31 kg |
| Warranty | 2 years warranty, Standard product exchange, including the battery |
| Rail Kit Included | includes rack kit and NMC card |
| Electrical Input | |
| Connection | (1) IEC-320-C20 |
| Input Voltage Without Using Batteries | 100/120/160/184 V to 284V |
| Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA). For active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively | |
| Input frequency Range Without Using Batteries | 40 to 70 Hz |
| Electrical Output | |
| Voltages | 230 V (adjustable to 200/208/220/240 V) |
| Outlets | (8) IEC-320-C13 |
| (1) IEC-320-C19 | |
| Remotely controlled sockets | 2 groups of 2 x IEC C13 (10A) on EX |
| Output Frequency | 50/60 Hz auto-select or frequency converter mode |
| Battery | |
| Battery Management | Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external battery units =>continuous maximisation of backup time + deep discharge protection |
| Communications | |
| User Interface | (3) LEDs + adjustable multilingual display: display of measurements, access to control and setup menus |
| Communication Ports | 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 serial ports cannot be used simultaneously) |
| 1 mini terminal block for remote ON/OFF and emergency stop | |
| Communications Card Slots | 1 slot for NMC Minislot card (included) or NMC ModBus/JBus or MC Contacts/Serial |
| Environmental & Standards | |
| Audible Noise | 45 dBA |
| Operating Temperature | 0°C to 40°C continuous |
| Performance - Safety - EMC | IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class |
| Approvals | CE, TüV, CB Report, UL |
Sold by ComX Computers