AP7922B specification sheet

Current Specials & Promotions
Product specification information

Specifications for AP7922B

APC Rack PDU, Switched, 2U, 32A, 230V, (16)C13

AP7922B Gallery image 1 [Size: 491 (W) x 129 (H)]  
APC RACK PDU, SWITCHED, 2U, 32A, 230V, (16)C13, 200, 208, 230, 230, 14.40(lbs) 6.55(kilos), 5.50x 20.00x 14.50(in) 14.00x 50.80x 36.80(cent)

UPS accessories

APC (American Power Convertion)

In Stock (not confirmed) Enquire now!
R 28 155.00 inc VAT

Features:

Manageability

  • Flash Upgradeable - Quickly and easily upgrade firmware via network download for future product enhancements. Eliminates the need to replace products already installed in the field when new features are released. (Note: Networked units only)
  • Remote Individual Outlet Control - Remotely manage outlets so users can turn outlets off that are not in use (prevent overloads) or recycle power to locked-up equipment (minimize costly downtime and avoid travel time to equipment).
  • Network Management Capabilities - Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet. Allows users to access, configure, and manage rack PDUs from remote locations to save valuable time. Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements.
  • Network port sharing - Allows four rack PDUs to be connected using In and Out ports so that only one network connection is necessary.
  • Integrates with StruxureWare Data Center Expert - An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network
  • Multi-tier user access - Supports up to four access levels - Administrator, Device User, Read-Only User and Network-only User - with user name and password requirements.
  • Local Current Monitoring Display - The aggregate current draw per rack PDU is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip. (Available on designated SKUs only)
  • Power Delays - Allows users to configure the sequence in which power is turned on or off for each outlet. This helps avoid in-rushes at start-up, which can cause overloaded circuits and dropped loads. Sequencing also allows users to predetermine which piece of equipment is turned on first so other equipment dependant on that unit will function properly.
  • Alarm Thresholds - Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems. (Note: Only available on units with the current monitoring capabilities. Please see SKU specifications for availability)

Adaptability

  • Rack-Mountable - Includes horizontal, vertical, and toolless-mount varieties. Puts power where it is needed most - in the racks near the equipment.
  • Wide range of input and output connections - Product family includes a variety of input and output connections to distribute 120V, 208V, or 230V power to multiple outlets. Having a variety of inputs and outputs allow users to adapt to varying power requirements. APC offers units that bring up to 14.4kW using a single branch whip.
  • Single input power source - Supply power from one branch whip to multiple pieces of equipment, conveniently powering rack-mount equipment. Saves time and money during installation by using one branch whip and standard connections.

Marketing Features

  • Power Delays - Allows users to configure the sequence in which power is turned on or off for each outlet. This helps avoid in-rushes at start-up, which can cause overloaded circuits and dropped loads. Sequencing also allows users to predetermine which piece of equipment is turned on first so other equipment dependant on that unit will function properly.
  • Remote Individual Outlet Control - Remotely manage outlets so users can turn outlets off that are not in use (prevent overloads) or recycle power to locked-up equipment (minimize costly downtime and avoid travel time to equipment).
  • Remote Management Capabilities - Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet. Allows users to access, configure, and manage units from remote locations to save valuable time. Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements.
  • Local Current Monitoring Display - The aggregate current draw per power distribution unit is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip.
  • Alarm Thresholds - Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems.

Specifications:

©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered.
Specificationsspacer
Product CodeAP7922Bspacer
Output
Nominal Output Voltage 230V
Maximum Total Current Draw 32
Output Connections (16) IEC 320 C13 (Battery Backup)
Input
Nominal Input Voltage 200V, 208V, 230V
Input frequency 50/60 Hz
Input Connections IEC 309 32A 2P+E
Cord Length 3.05meters
Acceptable Input Voltage 220-240VAC
Number of Power Cords 1
Load Capacity 7360VA
Maximum Input Current 32A
Physical
Maximum Height 89mm, 8.9CM
Maximum Width 445mm, 44.5CM
Maximum Depth 114mm, 11.4CM
Rack Height 2U
Net Weight 4.5KG
Shipping weight 6.55KG
Shipping Height 140mm, 14.0CM
Shipping Width 508mm, 50.8CM
Shipping Depth 368mm, 36.8CM
Color Black
Environmental
Operating Temperature 0 - 45 °C
Operating Relative Humidity 0 - 95 %
Operating Elevation 0-3000meters
Storage Temperature -25 - 65 °C
Storage Relative Humidity 0 - 95 %
Storage Elevation 0-15000meters
Conformance
Approvals CE, EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3, GOST, IRAM, MIC, VDE
Sustainable Offer Status
RoHS Compliant
REACH REACH: Contains No SVHCs
Battery Directive Compliant
Battery Notes ts_Battery_Notes