RCT-2000GTS specification sheet

Current Specials & Promotions
Product specification information

Specifications for RCT-2000GTS

RCT 2000GTS 1600W On-Line UPS

RCT-2000GTS Gallery image 1 [Size: 350 (W) x 447 (H)]  
RCT 2000GT On-Line UPS 1600W - Single phase with ground, LCD Display, 1 x RS232 & 1 x USB Port + SA Wall Socket

UPS 220V / 230V uninterrupted power supplies

RCT

Out of Stock
This product is no longer available for purchase. This information is for reference purposes only.
Click here to browse for similar products and for great alternatives!

Overview:

  • True double-conversion online UPS.
  • Wide input voltage range (110-300 VAC).
  • Input power factor correction 0.99.
  • Output Power Factor 0.8.
  • 50Hz/60Hz frequency converter mode.
  • Programmable power management outlets.
  • Emergency power off function (EPO).
  • ECO mode operation for energy saving (ECO).
  • SNMP+USB+RS-232 multiple communications.
  • Smart battery charger design.
  • Selectable output voltage via LCD panel.

Specifications:

©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered.
Product Code RCT-2000GT
Specifications
Model RCT-2000GT
Phase Single phase with ground
Capacity 2000 VA/1600 W
INPUT
Low Line Transfer 160 VAC ± 5% or 80 VAC ± 5% @ 100% load
Low Line Comeback 175 VAC ± 5% or 85 VAC ± 5% @ 100% load
High Line Transfer 300 VAC ± 5 % or 150 VAC ± 5 %
High Line Comeback 290 VAC ± 5 % or 145 VAC ± 5 %
Frequency Range 40 Hz ~ 70 Hz
Power Factor 0.99 @ Nominal Voltage (Full load)
OUTPUT
Output Voltage 208/220/230/240 VAC or 110/115/120/127 VAC
AC Voltage Regulation (Batt. Mode) ± 3%
Frequency Range (Synchronized Range) 47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
BATTERY
Battery Type & Number 12 V / 7 Ah x 6
Typical Recharge Time 4 hours recover to 90% capacity
PROTECTION
Full Protection Overload, discharge, and overcharge protection
MANAGEMENT
Smart RS-232 USB Supports Windows 2000/2003/XP/Vista/2008, Windows 7, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
DIMENSIONS
Height 220 mm
Width 145 mm
Depth 397 mm
Weight 13 kg