Specifications:
| © 2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. | |
Specifications for the product series![]() | |
| Product Code | SURT10000XLI![]() |
| Output | |
| Output Power Capacity | 8000 Watts / 10 kVA |
| Max Configurable Power | 8000 Watts / 10 kVA |
| Nominal Output Voltage | 230V |
| Output Voltage Note | Configurable for 220 : 230 or 240 nominal output voltage |
| Efficiency at Full Load | 0.92 |
| Output Voltage Distortion | Less than 3% |
| Output Frequency (sync to mains) | 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 |
| Other Output Voltages | 220240 |
| Crest Factor | 3:1 |
| Waveform Type | Sine wave |
| Output Connections | (1) Hard Wire 3-wire (H N + G) |
| (4) IEC 320 C13 | (4) IEC 320 C19 |
| (4) IEC Jumpers | Bypass |
| Input | |
| Nominal Input Voltage | 230V |
| Input Frequency | 50/60 Hz +/- 5 Hz (auto sensing) |
| Input Connections | Hard Wire 3 wire (1PH+N+G) |
| Hard Wire 5-wire (3PH + N + G) | Input voltage range for main operations |
| 160 - 280V | Other Input Voltages |
| 220240 | Input Total Harmonic Distortion |
| Batteries & Runtime | |
| Battery Type | Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
| Included Battery Modules | 4 |
| Typical recharge time | 2.20 hour(s) |
| Replacement Battery | RBC44 |
| RBC Quantity | 2 |
| Extended Run Options | APC Smart-UPS RT 10000VA 230V |
| Communications & Management | |
| Interface Port(s) | DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot |
| Pre-Installed SmartSlot Cards | AP9631 |
| Control panel | LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators |
| Audible Alarm | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
| Emergency Power Off (EPO) | Yes |
| Surge Protection and Filtering | |
| Filtering | Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
| Physical | |
| Maximum Height | 432.00 mm |
| Maximum Width | 263.00 mm |
| Maximum Depth | 736.00 mm |
| Rack Height | 6U |
| Net Weight | 110.91 KG |
| Shipping Weight | 129.09 KG |
| Shipping Height | 552.00 mm |
| Shipping Width | 597.00 mm |
| Shipping Depth | 991.00 mm |
| Color | Black |
| Units per Pallet | 1 |
| Environmental | |
| Operating Environment | 0 - 40 °C |
| Operating Relative Humidity | 0 - 95% |
| Operating Elevation | 0-3000 meters |
| Storage Temperature | -15 - 45 °C |
| Storage Relative Humidity | 0 - 95% |
| Storage Elevation | 0-15000 meters |
| Audible noise at 1 meter from surface of unit | 55.00 dBA |
| Online Thermal Dissipation | 2262.00 BTU/hr |
| Conformance | |
| Regulatory Approvals | C-tick, CE, EN 50091-1, EN 50091-2, EN 55022 Class A, EN 60950, EN 61000-3-2, GOST, VDE |
Sold by ComX Computers