Overview:
Effective 10-40kVA 3 phase UPS power protection against downtime and data loss for mission critical applications.
Features:
Field-replaceable power distribution panel
Ensures compatibility with equipment that has different plug types.
Locking cabinet
Prevents unauthorized access to the UPS.
Multiple cable-entry points
Provides flexibility of UPS placement in the room and easy access to install cabling to the terminal blocks.
Resettable circuit breakers
Enables a quick recovery from overload events.
Network manageable
Provides remote power management of the UPS over the network.
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
SmartSlot
Customize UPS capabilities with management cards.
Programmable frequency
Ensures compatibility with different input frequencies.
LED status indicators
Quickly understand unit and power status with visual indicators.
LCD display
Alpha-Numeric Display which displays system parameters and alarms.
Audible alarms
Provides notification of changing utility power and UPS power conditions
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Battery replacement without tools
Enables fast battery replacement, lowering Mean Time to Repair (MTTR).
Shippable with modules installed
Enables pre-installation UPS staging and testing and faster installation.
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
Cold-start capable
Provides temporary battery power when the utility power is out.
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Manual maintenance bypass
Reduces installation costs by eliminating the need for an external mechanical bypass.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Scalable runtime
Allows additional run time to be quickly added as needed.
Manual maintenance bypass
Reduces installation costs by eliminating the need for an external mechanical bypass.
Network manageable
Provides remote power management of the UPS over the network.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Scalable runtime
Allows additional run time to be quickly added as needed.
Specifications:
| ©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. | |
Specifications![]() | |
| Product Code | SUVTR40KHS![]() |
| Output | |
| Output power capacity | 32.0 KWatts / 40.0 kVA |
| Max Configurable Power (Watts) | 32.0 KWatts / 40.0 kVA |
| Nominal Output Voltage | 400V 3PH |
| Output Voltage Note | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage |
| Efficiency at Full Load | 0.96 |
| Output Voltage Distortion | Less than 5% at full load |
| Output Frequency (sync to mains) | 47 - 53 Hz for 50 Hz nominal |
| Output Frequency (not synced) | 50Hz +/- 0.1% for 50Hz nominal |
| Other Output Voltages | 380, 415 |
| Load Crest Factor | Unlimited |
| Topology | Double Conversion Online |
| Waveform type | Sine wave |
| Overload Operation | 60 seconds @ 125% and 30 seconds @ 150% |
| Maximum Output Current | 64 |
| Output Connections | (12) IEC 320 C19 (Battery Backup) |
| Bypass | Built-in Maintenance Bypass, Built-in Static Bypass |
| Input | |
| Nominal Input Voltage | 400V 3PH |
| Input frequency | 40 - 70 Hz (auto sensing) |
| Input Connections | Hard Wire 5-wire (3PH + N + G) |
| Input voltage range for main operations | 304 - 477V |
| Efficiency at Full Load | 0.96 |
| Other Input Voltages | 380, 415 |
| Maximum Input Current | 55.0A |
| Input Power Factor at Full Load | 0.98 |
| Batteries & Runtime | |
| Battery type | VRLA |
| Typical recharge time | 3hour(s) |
| Expected Battery Life (years) | 3 - 5 |
| Communications & Management | |
| Interface Port(s) | DB-9 RS-232, SmartSlot |
| Control panel | Multi-function LCD status and control console |
| Audible Alarm | Audible and visible alarms : configurable delays |
| Emergency Power Off (EPO) | Yes |
| Physical | |
| Maximum Height | 1995mm, 199.5CM |
| Maximum Width | 600mm, 60.0CM |
| Maximum Depth | 1075mm, 107.5CM |
| Net Weight | 289.0KG |
| Shipping weight | 370.91KG |
| Shipping Height | 2095mm, 209.5CM |
| Shipping Width | 756mm, 75.6CM |
| Shipping Depth | 1206mm, 120.6CM |
| Color | Black |
| Environmental | |
| Operating Temperature | 0 - 40 °C |
| Operating Relative Humidity | 0 - 95 % |
| Operating Elevation | 0-999.9meters |
| Storage Temperature | -50 - 40 °C |
| Storage Relative Humidity | 0 - 95 % |
| Storage Elevation | 0-15000meters |
| Audible noise at 1 meter from surface of unit | 67.0dBA |
| Online thermal dissipation | 5459.0BTU/hr |
| Protection Class | IP 20 |
| Conformance | |
| Approvals | C-tick, CE, EN 50091-2, EN/IEC 62040-3, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, ISO 9001, RCM, VFI-SS-111 |
Sold by ComX Computers