APC Symmetra LX 8kVA Scalable to 8kVA N+1 Tower, 220/230/240 or 380/400/415V, Input Voltage: 230, 400 3PH, Output Voltage: 230, Shipping Weight: 505.00(lbs) 229.56(kilos), Shipping Dimensions: 36.00x 23.60x 39.26(in) 91.40x 59.90x 99.70(cent)
UPS 220V / 230V uninterrupted power supplies
Features:
Removable input/output wiring tray
Allows quick and easy installation and maintenance of the UPS.
Availability
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
Configurable for N+1 internal redundancy
Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
Redundant Intelligence Modules
Provides higher availability to the UPS connected loads by giving redundant communication paths to critical UPS functions.
Hot-swappable intelligence modules
Ensures clean, uninterrupted power to protected equipment during Intelligence Module replacement.
Hot-swappable power modules
Ensures clean, uninterrupted power to protected equipment during Power Module replacement.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Power Modules connected in parallel
Enhances availability by allowing immediate, seamless recovery from isolated module failures.
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Automatic restart of loads after UPS shutdown
Automatically starts up the connected equipment upon the return of utility power.
Scalability
Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
Scalable runtime
Allows additional run time to be quickly added as needed.
Plug-and-Play external batteries
Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
Field-replaceable power distribution panel
Ensures compatibility with equipment that has different plug types.
Programmable frequency
Ensures compatibility with different input frequencies.
Manageability
Manageable external batteries
Reduces preventative maintenance service needs by monitoring the health and status of the external batteries and their expected runtime.
Network manageable
Provides remote power management of the UPS over the network.
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
LCD display
Alpha-Numeric Display which displays system parameters and alarms.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
SmartSlot
Customize UPS capabilities with management cards.
Serviceability
Predictive failure notification
Provides early-warning fault analysis ensuring proactive component replacement.
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Audible alarms
Actively let you know if the unit is on battery, if the battery is low or if there is an overload condition.
User-replaceable intelligence modules
Enables simple upgrades and replacements of the Intelligence Modules.
User-replaceable power modules
Enables simple upgrades and replacements of the Power Modules.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Disconnected battery notification
Warns when a battery is not available to provide backup power.
Protection
Power conditioning
Protects connected loads from surges, spikes, lightning, and other power disturbances.
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Generator compatible
Ensures clean, uninterrupted power to the loads in the event of an extended power outage
Cold-start capable
Provides temporary battery power when the utility power is out.
Resettable circuit breakers
Enables a quick recovery from overload events.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Specifications:
| ©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. | |
Specifications![]() | |
| Product Code | SYA8K8I![]() |
| Output | |
| Output Power Capacity | 5600 Watts / 8000 VA |
| Max Configurable Power | 5600 Watts / 8000 VA |
| Nominal Output Voltage | 230V |
| Output Voltage Note | Configurable for 220 : 230 or 240 nominal output voltage |
| Efficiency at Full Load | 0.9 |
| Output Voltage Distortion | Less than 5% at full load |
| Output Frequency (sync to mains) | 47 - 63 Hz |
| Other Output Voltages | 220, 240 |
| Crest Factor | up to 5 : 1 |
| Topology | Double Conversion Online |
| Waveform Type | Sine wave |
| Output Connections | (1) Hard Wire 3-wire (H N + G) |
| Bypass | Internal Bypass (Automatic and Manual) |
| Input | |
| Nominal Input Voltage | 230V, 400V 3PH |
| Input Frequency | 45 - 65 Hz (auto sensing) |
| Input Connections | Hard Wire 3 wire (1PH+N+G) |
| Hard Wire 5-wire (3PH + N + G) | |
| Input voltage range for main operations | 155 - 276 (1:1), 290 - 480 (3:1)V |
| Other Input Voltages | 220V, 240V, 380V, 415V |
| Input Total Harmonic Distortion | Less than 7% for full load |
| Batteries & Runtime | |
| Battery Type | Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
| Included Battery Modules | 2 |
| Typical recharge time | 3 hour(s) |
| Replacement Battery | SYBT5 |
| Communications & Management | |
| Interface Port(s) | DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot |
| Available SmartSlot Interface Quantity | 1 |
| Pre-Installed SmartSlot Cards | AP9631 |
| Control panel | Multi-function LCD status and control console |
| Audible Alarm | Audible and visible alarms prioritized by severity |
| Emergency Power Off (EPO) | Yes |
| Physical | |
| Maximum Height | 671.00 mm |
| Maximum Width | 483.00 mm |
| Maximum Depth | 726.00 mm |
| Net Weight | 201.82 KG |
| Shipping Weight | 229.56 KG |
| Shipping Height | 914.00 mm |
| Shipping Width | 599.00 mm |
| Shipping Depth | 997.00 mm |
| Color | Black, Silver |
| Environmental | |
| Operating Environment | 0 - 40 °C |
| Operating Relative Humidity | 0 - 95% |
| Operating Elevation | 0-3000 meters |
| Storage Temperature | -15 - 45 °C |
| Storage Relative Humidity | 0 - 95% |
| Storage Elevation | 0-4500 meters |
| Audible noise at 1 meter from surface of unit | 62.00 dBA |
| Online Thermal Dissipation | 2762.00 BTU/hr |
| Conformance | |
| Regulatory Approvals | C-tick, CE, EN 50091-1, EN 50091-2, EN 55022 Class A, EN 55024, EN 60950, GOST, IEC 60950, VDE |
| Sustainable Offer Status | |
| RoHS | Compliant |
Sold by ComX Computers
Specifications are subject to change without notice. E&OE. Prices are a guide only, and are valid on 2026-08-05 only, subject to stock being available. The specifications displayed above applies to the the entrie range, and may not apply to this specific model. Kindly note that options CANNOT be changed for most models, and some options are not available in South Africa.