UPS-ONL-2KVA-R-K specification sheet

Current Specials & Promotions
Product specification information

Specifications for UPS-ONL-2KVA-R-K

Linkqnet 2kva 48v Mp Rt 2u Rackmount Online Ups With 4x9ah Batteries

UPS-ONL-2KVA-R-K Gallery image 1 [Size: 991 (W) x 701 (H)]  
Linkqnet 2kva 48v Mp Rt 2u Rackmount Online Ups With 4x9ah Batteries

UPS 220V / 230V uninterrupted power supplies

LinkQnet

Out of Stock
This product is no longer available for purchase. This information is for reference purposes only.
Click here to browse for similar products and for great alternatives!

Overview summary:

The Linkqnet 2kVA 48V MP RT 2U Rackmount Online UPS is a high-performance power backup solution tailored for South African server rooms, network closets, and mission-critical systems. With true online double-conversion technology and full digital control, this UPS delivers seamless power continuity and protects sensitive equipment from voltage fluctuations, surges, and outages. It comes equipped with 4x 9Ah internal batteries, hot-swappable design, and intelligent fan control for efficient cooling.

Its 2U rack/tower convertible chassis makes it ideal for both vertical and horizontal mounting. The system includes advanced features such as a smart charger with expandable 12A current, versatile LCD interface, EPO support, and compatibility with generators. Its 0.99 input power factor, ECO mode, and cold start capability make it a reliable and energy-efficient choice for data environments demanding zero downtime.

UPS tier: Enterprise-grade Online Double Conversion UPS
UPS uses: Server protection, network infrastructure, medical systems, and industrial control

Features:

  • Rack/Tower convertible design online double conversion with full digital control
  • Wide input voltage range: 110~300Vac
  • Input power factor 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current can be expanded to 12A (Long run unit)
  • Emergency power-on function (EPO)
  • ECO mode operation for energy saving
  • Generator compatible
  • Hot-Swappable battery design
  • Cold start
  • Intelligent fan speed regulation
  • Load segment settable (Optional)
  • Versatile LCD human-computer interface
  • Multiple communication interfaces: RS232 (USB/EPO/Relay card/SNMP card optional)
  • Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm

Specifications:

©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered.
Specifications
Product Code UPS-ONL-2KVA-R-K
Details
Capacity 2000VA/1800W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~264Vac @ 100% load)
Power factor ≥0.99
FREQUENCY
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
OUTPUT
Output voltage 208/220/230/240Vac
Voltage regulation ±1%
Power factor 0.9
Output frequency Line mode : 46~54Hz or 56~64Hz
Battery mode : (50/60±0.1%)Hz
Crest factor 3::1
Harmonic distortion (THDv) ≤3% Linear load
≤5% Non linear load
Transfer time AC mode to Battery mode : 0ms
Inverter to Bypass : 4ms (Typical)
Output waveform Pure Sinewave
EFFICIENCY
AC mode 0.91
Battery mode 0.87
BATTERY
Battery number 4
Capacity (Standard unit) 9Ah 12V
Typical recharging time 4 hours (To 90% of full capacity)
Charging voltage 54.8Vdc±1%
Charging current (Max.) 1A
INDICATORS
LED display Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D x H 440 x 460 x 86.5mm
Net weight 19.5kg
ENVIRONMENT
Operating temperature 0°C~40°C
Storage temperature -25°C~55°C
Humidity range 20~95%RH @ 0°C~40°C (Non condensing)
Altitude < 1500m, derating required when&#-226;1500m
Noise level < 50dB at 1 Meter
STANDARDS
Safety IEC/EN 62040-1, IEC/EN 62477-1
EMC IEC/EN 62040-2 (IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2)