Linkqnet 3kva 72v Mp Xrt 2u Rackmount Online Ups - Requires Batteries
UPS 220V / 230V uninterrupted power supplies
Overview summary:
The LinkQnet 3KVA 72V MP XRT 2U Rackmount Online UPS delivers pure sinewave, double-conversion power for critical servers, network hardware, and high-performance equipment. With a wide input voltage range, selectable output voltages, and support for extended battery runtimes (batteries required), this smart UPS offers zero-transfer-time protection, generator compatibility, and energy-efficient ECO mode operation. It features hot-swappable batteries, intelligent charging up to 12A, and multiple communication interfaces, making it ideal for professional IT infrastructure and mission-critical environments.
UPS tier: Professional online double-conversion
Uses: Server protection, network stability, rackmount UPS setups, IT backup power, extended runtime battery systems
Features:
Specifications:
| ©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. | |
| Specifications | |
| Product Code | UPS-ONL-3KVA-XRT-K |
| Details | |
| Capacity | 3000VA/ 2700W |
| INPUT | |
| Nominal voltage | 208/220/230/240Vac |
| Input voltage range | 110~300Vac (176~280Vac @ 100% load) |
| Frequency range | 40~70Hz (50/60Hz Auto-Sensing) |
| Power factor | ≥0.99 |
| OUTPUT | |
| Output voltage | 208/220/230/240Vac |
| Power factor | 0.9 |
| Voltage regulation | ±1% |
| Output frequency | Line Mode : 46~54Hz or 56~64Hz |
| Bat. Mode : (50/60±0.1%)Hz | |
| Crest factor | 3::01 |
| Harmonic distortion (THDv) | ≤3% Linear load |
| ≤5% Non linear load | |
| Transfer time | AC mode to Bat.Mode : 0ms |
| Inverter to Bypass : 4ms (Typical) | |
| Output waveform | Pure Sinewave |
| EFFICIENCY | |
| AC mode | 0.92 |
| Battery mode | 0.88 |
| BATTERY | |
| 12V Series Battery number | 6 (72V) |
| Battery Capacity (typical) | 9Ah to 200Ah |
| Typical recharging time | 4 hours (to 90% of full capacity based on battery capacity) |
| Charging voltage | 82.2Vdc+-1% |
| Charging current (Max) | 12A |
| INDICATORS | |
| LED display | Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload and UPS fault |
| LCD display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage |
| Battery voltage, Inner temperature and Remaining battery backup time | |
| ALARM | |
| Battery mode | Beeping every 4 seconds |
| Battery low | Beeping every second |
| Overload | Beeping twice every second |
| Fault | Continously beeping |
Sold by ComX Computers
Specifications are subject to change without notice. E&OE. Prices are a guide only, and are valid on 2026-08-07 only, subject to stock being available. The specifications displayed above applies to the the entrie range, and may not apply to this specific model. Kindly note that options CANNOT be changed for most models, and some options are not available in South Africa.